3.1 Overview
3 Modbus/TCP - Data areas
33000Modbus/TCP - Data areasModbus/TCP - Data areas3-3.1Overview3100Overview3-ModbusTCP_Modbus/TCP-Datenbereiche-PNOZmulti
A modular safety system PNOZmulti supports the following Modbus/
TCP data areas:
Data area Modbus syntax Example
Coils (Bit)
0x00000 … 0x65535
[read/write]
0x[xxxxx] 0x00031
(virtual input i31)
Discrete Inputs (Bit)
1x00000 … 1x65535
[read only]
1x[xxxxx] 1x08193
(virtual output o1)
Input Register (Word/16 Bits)
3x00000 … 3x65535
[read only]
3x[xxxxx] 3x00002
(virtual inputs 32 ... 47)
Holding Register (Word/16 Bits)
4x00000 … 4x65535
[read/write]
4x[xxxxx] 4x00805
(project name, 1st character)
INFORMATION
Addressing for PNOZmulti systems starts at “0”. On devices
from other manufacturers, addressing can start at “1”.
Please refer to the operating manual provided by the relevant
manufacturer.