Wiring
OperatingManualPSSuEF4DI(T)(R)
21310EN05
20
6 Wiring
6.1 Generalwiringguidelines
Pleasenote:
}
Appropriatewiringmustbeusedtoexcludeshortcircuitsbetweenthetestpulseout
putsandthecorrespondinginput!
}
Appropriatewiringmustbeusedtoexcludeshortcircuitsbetweentheinputsortoa
supplyline!
}
Thecablerunsforthetestpulsesmaybemax.200m.
}
Signallinesdonothavetobeshielded.
}
Usecopperwiring.
6.1.1 Mechanicalconnectionofthebasemodules
Procedure:
}
Useaflatbladescrewdriver(DIN5264A)!
}
Stripthewireback8mm.
}
Ifnecessary,labeltheconnectionlevelwithacolourmarker[3].
}
Basemodulewithscrewterminals:
– Useascrewdrivertoloosenthescrewonthescrewterminal[1]
– Insertthestrippedcableintotheroundfixinghole[2],asfarasitwillgo.
– Tightenupthescrewonthescrewterminal.
– Checkthatthecableisfirmlyseated.
}
Basemodulewithcageclampterminals:
– Insertthescrewdriver[4]intothesquarehole[1].
– Insertthestrippedcableintotheroundfixinghole[2],asfarasitwillgo[5].
– Pulloutthescrewdriver[6].
– Checkthatthecableisfirmlyseated.