6-1
6.1 General wiring guidelines
6 Wiring
66000WiringWiring6-6.1General wiring guidelines6100General wiring guidelines6-][Verdrahtung BA Einleitung
Please note:
][Verdrahtung PD1
Safe electrical isolation must be ensured for the external supplies.
Failure to do so could result in electric shock.
The external power supplies must comply with the current applicable
standard EN 60950-1, EN 61140, EN 50178 or EN 61558-1.
The maximum current load on the connection terminals is 4 A per
supply.
Permitted infeed at the module's connection terminals:
–PE
–0V
–Shield
- 30 VDC ... + 30 VDC
- 48 VAC ... + 48 VAC
Use copper wiring.
][Verdrahtung Zusatz ohne C
The terminal configuration as stated on the front plate applies for base
modules without C-rail. The terminal configuration as stated in the
technical documentation applies for all other base modules.
6.1.1 Mechanical connection of the base modules
Mechanical connection of the base modules6-][Modulverdrahtung mech
Procedure:
Use a flat blade screwdriver (DIN 5264-A)!
Strip the wire back 8 mm.
If necessary, label the connection level with a colour marker [3].
Base module with screw terminals:
Use a screwdriver to loosen the screw on the screw terminal [1]
Insert the stripped cable into the round fixing hole [2], as far as it
will go.
Tighten up the screw on the screw terminal.
Check that the cable is firmly seated.