Wiring
Operating Manual PSSu E F BSW(-T)
21372-EN-05
23
Switching an earthed actuator
















On earthed actuators, the actuator's 0 V connection must be connected to 0 V of the pe-
riphery supply (external supply voltage).
Reason: The switch (0 V periphery supply) in the PSSu E F BSW module is bridged when
the actuator's earthed 0 V connection is connected to 0 V on the connected periphery sup-
ply. In this case, the PSSu E F BSW registers a short circuit between 0 V of the external
supply voltage and 0 V of the connected periphery supply.
Error reaction: The PSSu will not start and all affected I/O-Groups (SafetyBUS p) remain in
a STOP condition.