Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
3-1
3.1 Intended use
3 Safety
33000SafetySafety3-3.1Intended use3100Intended use3-Bestimmung/Gertebeschreibung_multi_Drehzahlwaechter
The expansion module monitors standstill, speed and direction of rota-
tion in accordance with EN ISO 13849-1 up to PL e and EN IEC 62061
up to SIL CL 3.
Bestimmung/Gertebeschreibung_multi_Zusatz_Modul
The expansion module may only be connected to a base unit from the
configurable control system PNOZmulti.
Bestimmung/Gertebeschreibung_multi_System
The configurable control system PNOZmulti is used for the safety-relat-
ed interruption of safety circuits and is designed for use in:
E-STOP equipment
Safety circuits in accordance with VDE 0113 Part 1 and EN 60204-1
Bestimmung/Gertebeschreibung_multi_Drehzahlwchter_Warnungen_ms3_4p_BA
WARNING!
Users must take appropriate measures to detect or exclude
errors (e.g. slippage or broken shearpin) which cause the fre-
quency of the encoder signal to no longer be proportional to the
monitored speed.
Appropriate measures are:
Using the monitored encoder to also control the drive
Mechanical solutions
WARNING!
Encoder errors are detected and signalled via a diagnostic bit.
This does does notbring the relevant axis to a safe condition.
To maintain safety (Category 3), the diagnostic bit (diagnostic bit
10) in the user program must be evaluated in such a way that a
shutdown occurs if the axis is in operation (see examples in
Chapter 9).
CAUTION!
If there are frequency differences between tracks A and B of the
incremental encoder, the track with the higher frequency will be
evaluated. Different directions of rotation will no longer be
detected. The outputs
Clockwise
and
Anti-clockwise
switch
to a safe condition. The safe condition is cleared again as soon
as the error is remedied. Hazards that can arise through an auto-
matic restart must be excluded within the user program.