FieldbusModules
OperatingManualPNOZmulti2CommunicationInterfaces
1002971EN02
19
4.2.2 Accesstotablesegments
ThedataintheTables[
101]canberequestedviathefollowingobjects.
Inputdata
TheMasterrequestsatablesegmentintheform:
Description InputdatafromPNOZmulti2
Tableandsegmentnumber 2InputBytes
Outputdata
ThePNOZmulti2repliesintheform:
Description OutputdatafromPNOZmulti2
Tableandsegmentnumber+13Bytepayload 15OutputBytes
AdetaileddescriptionisavailableinthechapterentitledAccesstotablesegments[
15].
4.2.3 LEDstatus
TheLEDstatusofthePNOZmulti2canberequesteddirectlyviathefollowingobject.
Description OutputdatafromPNOZmulti2
LEDstatus 1OutputByte
}
Bit0=1:LEDOFAULTislitorflashes
}
Bit1=1:LEDIFAULTislitorflashes
}
Bit2=1:LEDFAULTislitorflashes
}
Bit3=1:LEDDIAGislitorflashes
}
Bit4=1:LEDRUNislit
}
Bit57:Reserved
4.2.4 DiagnosticdataPNOZmESProfibus
Thesebitscontainthediagnosticdata
Un
it_Diag_Bit
Content
00 RUN,baseunitisinRUNcondition
01 STOP,baseunitisinSTOPcondition
02 BaseunitwasstoppedbytheConfigurator
03 Reserved
04 Externalerror
05 Internalerror
06 Externalerrorontheinputs