Pilz PSSu H SB IBSe User Manual Page 26

  • Download
  • Add to my manuals
  • Print
  • Page
    / 39
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 25
7.1 Messages
7 Operation
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
7-2
(
1
) There are two levels of overtemperature.
Too warm:
If a module's temperature exceeds a threshold value, the module
sends a warning to the head module. If the temperature drops back
below the threshold value, the module sends an all-clear.
Too hot:
If a module's temperature exceeds a further threshold value, the mod-
ule sends an error message to the head module and triggers an I/O-
Group stop.
Further information on PSSu error messages is available in the online
help for the system software.
Overload of the supply voltage for en-
coder
Supply voltage for encoder overload-
ed or short-circuited
Rectify overload or short circuit
Overvoltage error A system voltage or infeed is too high Stabilise the supply or change the
faulty supply voltage module
Undervoltage error A system voltage or infeed is too low Stabilise the supply or change the
faulty supply voltage module
Error in the overvoltage protection di-
odes
Overvoltage protection diodes are de-
fective
Change faulty supply voltage module
Timeout error on the output No data has been received for the out-
put from the module bus for longer
than 50 ms.
Check ST communication or configu-
ration
Polarity error Polarity of the periphery supply Correct the polarity
Error in the periphery supply Lower voltage limit exceeded on the
periphery supply
Ensure there is a sufficient supply
Module error Statement Remedy