PZEX4
OperatingManualPZEX4
1003199EN08
5
INFORMATION
Thisgivesadviceonapplicationsandprovidesinformationonspecialfea
tures.
Intendeduse
TheunitmeetstherequirementsofEN6094751,EN602041andVDE01131.Thecon
tactexpansionmoduleisusedtoincreasethenumberofinstantaneoussafetycontacts
availableonabaseunit.Baseunitsareallsafetyrelayswithfeedbackloopmonitoring.
ThecategorythatcanbeachievedinaccordancewithENISO138491dependsonthe
categoryofthebaseunit.Thecontactexpansionmodulemaynotexceedthis.
Foryoursafety
}
Onlyinstallandcommissiontheunitifyouhavereadandunderstoodtheseoperating
instructionsandarefamiliarwiththeapplicableregulationsforhealthandsafetyatwork
andaccidentprevention.
EnsureVDEandlocalregulationsaremet,especiallythoserelatingtosafety.
}
Anyguaranteeisrenderedinvalidifthehousingisopenedorunauthorisedmodifica
tionsarecarriedout.
}
NoteforovervoltagecategoryIII:Ifvoltageshigherthanlowvoltage(>50VACor>120
VDC)arepresentontheunit,connectedcontrolelementsandsensorsmusthavea
ratedinsulationvoltageofatleast250V.
Unitfeatures
}
Positiveguidedrelayoutputs:
– 4safetycontacts(N/O),instantaneous
}
LEDdisplayfor:
– Switchstatuschannel1/2
}
Connectionforfeedbackloop
}
Operation:singlechannel
Safetyfeatures
Theunitmeetsthefollowingsafetyrequirements:
}
Thecontactexpandermoduleexpandsanexistingcircuit.Astheoutputrelaysare
monitoredviathebaseunit'sfeedbackloop,thesafetyfunctionsontheexistingcircuit
aretransferredtothecontactexpandermodule.
}
Thesafetyfunctionremainseffectiveinthecaseofacomponentfailure.
}
Earthfaultinthefeedbackloop:
Detected,dependingonthebaseunitthatisused.
}
Earthfaultintheinputcircuit:
Theoutputrelaysdeenergiseandthesafetycontactsopen.
Comments to this Manuals