Installation
}
TheunitshouldbeinstalledinacontrolcabinetwithaprotectiontypeofatleastIP54.
}
UsethenotchontherearoftheunittoattachittoaDINrail.
}
EnsuretheunitismountedsecurelyonaverticalDINrail(35mm)byusingafixingele
ment(e.g.retainingbracketoranendangle).
}
Ifmorethan2unitsareinstallednexttoeachotherinthecontrolcabinet,leaveadis
tanceofatleast6mmbetweentheunits.
Wiring
Pleasenote:
}
Informationgiveninthe"Technicaldetails[ 9]"mustbefollowed.
}
Theoutputs1314,2324,3334and4344aresafetycontacts.
}
Topreventcontactwelding,afuseshouldbeconnectedbeforetheoutputcontacts(see
Technicaldetails).
}
Calculationofthemax.cablerunsl
max
intheinputcircuit:
R
lmax
R
l
/ km
I
max
=
R
lmax
=max.overallcableresistance(seeTechnicaldetails)
R
l
/km=cableresistance/km
}
Usecopperwirethatcanwithstand60/75°C.
}
Sufficientfuseprotectionmustbeprovidedonalloutputcontactswithcapacitiveandin
ductiveloads.
}
Donotswitchlowcurrentsusingcontactsthathavebeenusedpreviouslywithhighcur
rents.