Page view 21
Wiring
Operating Manual PSSu E F BSW(-T)
21372-EN-05
22
Terminal configuration
} Supply module
To switch on/off the periphery supply to input/output blocks (block switching)
To interrupt the incoming (left-hand) periphery supply and C-rail supply
To provide subsequent (right-hand) modules with the periphery supply and C-rail
supply
Base module Terminal configuration
Screw terminals:
PSSu BS 2/8S
PSSu BS 2/8S-T
Cage clamp terminals:
PSSu BS 2/8C
PSSu BS 2/8C-T
11: Not assigned
21: Not assigned
12-22: 0 V periphery supply,
interrupted to the left
(12-22 linked within the base
module)
13-23: +24 V periphery sup-
ply,
interrupted to the left
(13-23 linked within the base
module)
14-24: C-rail supply,
interrupted to the left
(14-24 linked within the base
module)




6.2